ENGINEERING TOOL / P = ρ × g × h
Hydrostatic Level Calculator & Installation Guide
Convert liquid level to pressure or pressure to depth in m, ft, kPa, bar and psi. Understand specific gravity and protect the atmospheric vent tube.
CALCULATED GAUGE LIQUID COLUMN
0.98066 bar
14.2233 psi
10.0000 m
32.8084 ft
P = 1000 × 1 × 9.80665 × 10.0000 Pa
Use this liquid head in my RFQ ↗Convert the column above the probe, not the total well depth.
A vented hydrostatic level sensor measures gauge pressure relative to atmospheric pressure. With a known density, h = P / (ρg). This tool assumes constant density, standard gravity 9.80665 m/s² and an atmospheric liquid surface. It does not compensate sealed-tank headspace pressure or calculate tank volume.
| Liquid | SG | kPa gauge | bar gauge |
|---|---|---|---|
| Water | 1.00 | 98.0665 | 0.980665 |
| Diesel example | 0.84 | 82.37586 | 0.8237586 |
| Sulfuric acid example | 1.84 | 180.44236 | 1.8044236 |
Density presets are arithmetic examples. Use actual process density at operating temperature; the acid preset provides no materials approval.
Keep the atmospheric vent open, dry and above flood level.
- Fix the sensor at the required datum; account for sediment, turbulence and cleaning access.
- Route the cable without crushing or tight bends. Do not pull on conductors or the atmospheric vent.
- Terminate above flood level in an appropriate weatherproof, breathable enclosure. Never seal, kink or submerge the cable vent end.
- Fit suitable moisture protection and inspect the desiccant/filter for the actual humidity and service interval.
- Check wiring, supply, PLC scaling, grounding and low/high reference levels before commissioning.
A sealed junction box without a breathable atmospheric path defeats a vented gauge sensor. Cable splicing and termination changes require the configured manufacturer's instructions.
Specify the vented termination kit ↗Technical references and scope
WIKA: moisture protection for the cable and vent tube ↗WIKA: LS-10 submersible pressure measurement ↗References explain the measurement principle and installation risks. They do not qualify SubmersibleLevel product performance.
KEEP THE WHOLE LOOP IN VIEW
From probe selection to dry cable termination.
START WITH THE INSTALLATION
Liquid. Depth. Cable. Signal.
Send these four inputs to start a configuration review.