Hydrostatic Level Calculator & Installation Guide

Convert liquid level to pressure or pressure to depth in m, ft, kPa, bar and psi. Understand specific gravity and protect the atmospheric vent tube.

Density varies with temperature and concentration. Presets are illustrative, not chemical compatibility approvals.

CALCULATED GAUGE LIQUID COLUMN

98.0665kPa

0.98066 bar

14.2233 psi

10.0000 m

32.8084 ft

P = 1000 × 1 × 9.80665 × 10.0000 Pa

Use this liquid head in my RFQ ↗

Convert the column above the probe, not the total well depth.

A vented hydrostatic level sensor measures gauge pressure relative to atmospheric pressure. With a known density, h = P / (ρg). This tool assumes constant density, standard gravity 9.80665 m/s² and an atmospheric liquid surface. It does not compensate sealed-tank headspace pressure or calculate tank volume.

Worked example: 10 m liquid head, illustrative constant density
LiquidSGkPa gaugebar gauge
Water1.0098.06650.980665
Diesel example0.8482.375860.8237586
Sulfuric acid example1.84180.442361.8044236

Density presets are arithmetic examples. Use actual process density at operating temperature; the acid preset provides no materials approval.

Keep the atmospheric vent open, dry and above flood level.

  1. Fix the sensor at the required datum; account for sediment, turbulence and cleaning access.
  2. Route the cable without crushing or tight bends. Do not pull on conductors or the atmospheric vent.
  3. Terminate above flood level in an appropriate weatherproof, breathable enclosure. Never seal, kink or submerge the cable vent end.
  4. Fit suitable moisture protection and inspect the desiccant/filter for the actual humidity and service interval.
  5. Check wiring, supply, PLC scaling, grounding and low/high reference levels before commissioning.

A sealed junction box without a breathable atmospheric path defeats a vented gauge sensor. Cable splicing and termination changes require the configured manufacturer's instructions.

Specify the vented termination kit ↗

Technical references and scope

WIKA: moisture protection for the cable and vent tube ↗WIKA: LS-10 submersible pressure measurement ↗

References explain the measurement principle and installation risks. They do not qualify SubmersibleLevel product performance.